Place of Origin:
China (Mainland)
Nama merek:
Kacise
Sertifikasi:
certificate of explosion-proof,
Model Number:
M18 KUS1000
Sensing range | 100... 1000 mm |
Adjustment range | |
Unusable area | 0 ... 100 mm |
Standard target plate | 100 mm x 100 mm |
Transducer frequency | approx.220 kHz |
Response delay | approx. 50 ms |
LED blue | power-on |
LED yellow |
indication of the switching state flashing: program function object detected |
LED red |
permanently red: Error Red,flashing:program function,object not detected |
Operating voltage UB | 15 ... 30 V DC , ripple 10 %SS |
No-load supply current I0 | ≤ 45 mA |
Input type | 1 TEACH-IN input |
operating range A1: -UB ... +1 V, operating range A2: +6 V ... +UB |
|
input impedance: > 4.7 kΩ ; TEACH-IN program pulse: ≥ 1 s |
Output type | 1 switch output E4, NPN NO/NC,programmable |
Rated operating current Ie | 200 mA , short-circuit/overload protected |
Default setting | Switching point A1:70mm Switching point A2: 800mm |
Voltage drop | ≤ 2.5 V |
Repeat accuracy | ≤1 % |
Switching frequency f | ≤ 13 Hz |
Range hysteresis H | 2 % of the set operating distance |
Temperature influence | ±1.5% of full-scale value |
Ambient temperature | -25…70℃(248...343K) |
Storage temperature | -40…85℃(233...358K) |
Connection | V1 connector(M12×1),4-pin |
Protection degree | IP67 |
Material Housing | brass, nickel-plated |
Transducer |
epoxy resin/hollow glass sphere mixture; foam polyurethane, cover PBT |
The ultrasonic sensor features a switch output with two teachable switching points. These are set by applying the supply voltage - UB or + UB to the TEACH-IN input. The supply voltage must be applied to the TEACH-IN input for at least 1 s.LEDs indicate whether the sensor has recognised the target during the TEACH-IN procedure. Switching point A1 is taught with - UB,A2 with +UB. Eight different output functions can be set. Switching point, Setting distance only after power on. The internal clock can assure can't be changed after 5 mins when power on. If want to change the switching point, the user can only setting the request distance after power restart.
TEACH-IN window mode, normally-open function
- Set target to near switching point
- TEACH-IN switching point A1 with - UB
- Set target to far switching point
- TEACH-IN switching point A2 with + UB
TEACH-IN window mode, normally-closed function
- Set target to far switching point
- TEACH-IN switching point A2 with - UB
- Set target to near switching point
- TEACH-IN switching point A1 with + UB
TEACH-IN switching point, normally-open function
- Set target to near switching point
- TEACH-IN switching point A1 with - UB
- Cover sensor with hand or remove all objects
from sensing range
- TEACH-IN switching point A2 with + UB
TEACH-IN switching point, normally-closed function
- Cover sensor with hand or remove all
objects from sensing range
- TEACH-IN switching point A2 with - UB
- Set target to near switching point
- TEACH-IN switching point A1 with + UB
TEAC-IN large hysteresis interval, normally-open mode
- Set target to near switching point
- TEACH-IN switching point A1 with + UB
- Set target to far switching point
- TEACH-IN switching point A2 with - UB
TEAC-IN large hysteresis interval, normally-closed mode
- Set target to far switching point
- TEACH-IN switching point A2 with + UB
- Set target to near switching point
- TEACH-IN switching point A1 with - UB
TEACH-IN detection of objects presence normally open mode
- Cover sensor with hand or remove all objects from
sensing range
- TEACH-IN switching point A2 with - UB
- Cover sensor with hand or remove all objects from
sensing range
- TEACH-IN switching point A2 with + UB
TEACH-IN detection of objects presence normally closed mode
- Cover sensor with hand or remove all objects from sensing range
- TEACH-IN switching point A2 with +UB
- Cover sensor with hand or remove all objects from sensing range
- TEACH-IN switching point A2 with -UB
Default setting of switching point
A1=blind range,A2=nominal distance
LED displays | ||
Displays in dependence on operating mode | Red LED | Yellow LED |
TEACH-IN switching point Object detected No object detected Object uncertain(TEACH-IN invalid) |
off flashes On |
flashes off off |
Normal operation | off | Switching state |
Fault | on | Previous state |
5. Installation conditions
If the sensor is installed at the environment temperature fall below 0℃,It should do well on the protective measures. In case of direct mounting of the sensor in a through hole using the steel nuts, it has to be fixed at the middle of the housing thread.
Kirim pertanyaan Anda langsung ke kami